Group – Simple Duct Model
Overview
The Simple Duct model provides the ability to simulate duct conduction and leakage losses in an AirLoop (i.e., AirLoopHVAC object) without using Airflow Network model. There are 4 types of conduction ducts and 4 types of duct leakages. Their definitions are provided below:
Duct conduction definitions:
Supply Trunk duct: The connection of SupplyTrunk is between the inlet node (AirloopHVAC Demand Side Inlet Node) of AirLoopHVAC and the AirLoopHVAC:ZoneSplitter. A single supply trunk is specified. In other words, there is a single supply trunk for each AirLoopHVAC.
Supply Branch duct: The connection of SupplyBranch is between the AirLoopHVAC:ZoneSplitter and the inlet node of a zone terminal. Each outlet of the AirLoopHVAC:ZoneSplitter has a single branch duct. The number of Supply Branch ducts are the same as the number of outlets of the AirLoopHVAC:ZoneSplitter for each AirLoopHVAC.
Return Branch duct: The connection of ReturnBranch is between the zone outlet node and the AirLoopHVAC:ZoneMixer. Each outlet of the AirLoopHVAC:ZoneMixer has a single branch duct.The number of Return Branch ducts are the same as the number of inlets of the AirLoopHVAC:ZoneMixer for each AirLoopHVAC
Retun Trunk duct: The connection of ReturnTrunk is between AirLoopHVAC:ZoneMixer and the outlet node (AirloopHVAC Demand Side Outlet Node) of AirLoopHVAC. A single return trunk is specified. In other words, there is a single return trunk for each AirLoopHVAC.
Duct leakage definitions:
Supply Trunk leak: The supply trunk duct leak occurs at the end of supply trunk duct. The leak is originated at the AirLoopHVAC:ZoneSplitter and terminated at a zone or outdoors.
Supply Branch leak: The supply branch duct leak occurs at the end of supply branch duct. The leak is originated at the zone terminal inlet node and terminated at a zone or outdoors.
Return Branch leak: The return branch duct leak occurs at the beginning of return branch duct. The leak is originated at a zone or outdoors and terminated at the zone outlet node.
Return Trunk leak: The return trunk duct leak occurs at the beginning of return trunk duct. The leak is originated at a zone or outdoors and terminated at the AirLoopHVAC:ZoneMixer.
Model assumptions are provided below:
The calculation of leakage loss is based solely on energy transfer, with no involvement of mass flows in either the AirLoopHVAC system or zones. For instance, when a supply leak occurs, the supply flow rate remains constant throughout all supply ducts and zone terminals. However, the energy losses from the supply leak are incorporated into the system’s requested load to ensure energy and zone balance in a controlled zone. It is important to note that energy conservation is upheld in duct leakage scenarios, while mass flow rates remain unchanged, even in the presence of supply duct leaks.
Any energy losses for supply leak is originated at the end of the source duct and terminated in the target zone or outdoor air node only. Two types of supply leaks are allowd: Trunk and Branch.
Any energy losses for return leak is originated in a zone or outdoor and terminated at the beginning of the source duct. Two types of return leaks are allowd: Trunk and Branch.
Any air movement between zones caused by duct leakage can be accomplished by Duct:Loss:MakeupAir objects.
Other input rules
Every Duct:Loss:* object requires a corresponding AirflowNetwork:Distribution:Linkage object.
The AirflowNetwork:Distribution:Linkage objects must reference an AirflowNetwork:Distribution:Component:Duct object which specifies the duct properties.
The Duct:Loss:Conduction objects for a given duct linkage should reference the same AirflowNetwork:Distribution:Component:Duct object.
The Duct:Loss:Leakage objects for a given duct linkage should reference the same AirflowNetwork:Distribution:Component:LeakageRatio object.
Duct:Loss:Conduction
This object allows users to input ducts with conduction loss only for simplified duct model.
Field: Name
The name identifies the duct for later reference and in the output listing. Each duct loss should have a unique name.
Field: AirLoopHAVC Name
The name of an AirLoopHVAC object, which is also defined in a AirLoopHVAC object.
Field: AirflowNetwork:Distribution:Linkage Name
The name of an AirflowNetwork:Distribution:Linkage object, which is also defined in a AirflowNetwork:Distribution:Linkage object.
Field: Environment Type
Environment type is the environment in which the duct is placed. It can be either Zone or Schedule. If specified as Zone, a zone name must be specified in the next field. If specified as Schedule, the Ambient Temperature Zone can be left blank, while a schedule must be specified for the temperature.
Field: Ambient Zone Name
If Zone is specified as the environment type, this field is used to specify the name of the zone in which the duct is located. The zone temperature and humidity ratio are used to calculate the heat and moisture transfer rate from the duct, respectively.
Field: Ambient Temperature Schedule Name
If Schedule is specified as the environment type, this field is used to specify the name of the temperature schedule that gives the ambient air temperature surrounding the duct. This temperature is used as the outside boundary condition to calculate heat transfer from the duct.
Field: Ambient Humidity Ratio Schedule Name
If Schedule is specified as the environment type, this field is used to specify the name of the humidity ratio schedule that gives the ambient air humidity ratio surrounding the duct. This humidity ratio is used as the outside boundary condition to calculate moisture transfer from the duct.
An IDF example is provided below:
Duct:Loss:Conduction,
Main duct, !- Name
Main AirLoopHVAC, !- AirLoopHAVC Name
Main Link, !- AirflowNetwork:Distribution:Linkage Name
Zone, !- Environment Type
Zone 1, !- Ambient Zone Name
, !- Ambient Temperature Schedule Name
; !- Ambient Humidity Ratio Schedule Name
AirflowNetwork:Distribution:Linkage,
Main Link, !- Name
EquipmentInletNode, !- Node 1 Name
SplitterNode, !- Node 2 Name
MainTruck, !- Component Name
Attic Zone; !- Thermal Zone Name
AirflowNetwork:Distribution:Node,
EquipmentInletNode, !- Name
Zone Equipment Inlet Node, !- Component Name or Node Name
Other, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
SplitterNode, !- Name
, !- Component Name or Node Name
AirLoopHVAC:ZoneSplitter, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Component:Duct,
MainTruck, !- Name
2.0, !- Duct Length {m}
0.4064, !- Hydraulic Diameter {m}
0.1297, !- Cross Section Area {m2}
0.0009, !- Surface Roughness {m}
0.01, !- Coefficient for Local Dynamic Loss Due to Fitting {dimensionless}
0.946792, !- Heat Transmittance Coefficient (U-Factor) for Duct Wall Construction {W/m2-K}
0.0000001, !- Overall Moisture Transmittance Coefficient from Air to Air {kg/m2}
5.018000, !- Outside Convection Coefficient {W/m2-K}
25.090000; !- Inside Convection Coefficient {W/m2-K}
The objects required for a complete set of inputs to simulate duct conduction losses are listed below
Duct:Loss:Conduction
AirflowNetwork:Distribution:Linkage
AirflowNetwork:Distribution:Node
AirflowNetwork:Distribution:Component:Duct
Duct:Loss:Leakage
This object allows users to input duct leaks only for simplified duct model.
Field: Name
The name identifies the duct leak for later reference and in the output listing. Each duct leak should have a unique name.
Field: AirLoopHAVC Name
The name of a AirLoopHVAC object, which is also defined in a AirLoopHVAC object.
Field: AirflowNetwork:Distribution:Linkage Name
The name of an AirflowNetwork:Distribution:Linkage object, which is also defined in a AirflowNetwork:Distribution:Linkage object.
An IDF example is provided below:
Duct:Loss:Leakage,
Supply leak, !- Name
Typical Residential System, !- AirLoopHVAC name
ZoneSupplyLeakLink; !- AirflowNetwork:Distribution:Linkage name
AirflowNetwork:Distribution:Linkage,
ZoneSupplyLeakLink, !- Name
SplitterNode, !- Node 1 Name
Attic Zone, !- Node 2 Name
SupplyLeak; !- Component Name
AirflowNetwork:Distribution:Node,
SplitterNode, !- Name
, !- Component Name or Node Name
AirLoopHVAC:ZoneSplitter, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
Attic Zone, !- Name
Attic Zone, !- Component Name or Node Name
Zone, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Component:LeakageRatio,
SupplyLeak, !- Name
0.1, !- Effective Leakage Ratio {dimensionless}
1.9, !- Maximum Flow Rate {m3/s}
60, !- Reference Pressure Difference {Pa}
0.65; !- Air Mass Flow Exponent {dimensionless}
The objects required for a complete set of inputs to simulate duct leakage losses are listed below
Duct:Loss:Leakage
AirflowNetwork:Distribution:Linkage
AirflowNetwork:Distribution:Node
AirflowNetwork:Distribution:Component:LeakageRatio
Duct:Loss:MakeupAir
This object allows users to input makeup air caused by a sum of supply leaks greater than a sum of return leaks only for simplified duct model.
Field: Name
The name identifies the makeup air for later reference and in the output listing. Each duct leak should have a unique name.
Field: AirLoopHAVC Name
The name of a AirLoopHVAC object, which is also defined in a AirLoopHVAC object.
Field: AirflowNetwork:Distribution:Linkage Name
The name of an AirflowNetwork:Distribution:Linkage object, which is also defined in a AirflowNetwork:Distribution:Linkage object.
An IDF example is provided below:
Duct:Loss:MakeupAir,
ReturnMakeup, !- Name
Typical Residential System, !- AirLoopHVAC name
ReturnMakeupLink; !- AirflowNetwork:Distribution:Linkage name
AirflowNetwork:Distribution:Linkage,
ReturnMakeupLink, !- Name
OutdoorNode, !- Node 1 Name
Garage Zone, !- Node 2 Name
ReturnMakeupAir; !- Component Name
AirflowNetwork:Distribution:Node,
Garage Zone, !- Name
Garage Zone, !- Component Name or Node Name
Zone, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Node,
OutdoorNode, !- Name
Outside Air Inlet Node, !- Component Name or Node Name
OutdoorAir:Node, !- Component Object Type or Node Type
3.0; !- Node Height {m}
AirflowNetwork:Distribution:Component:LeakageRatio,
ReturnMakeupAir, !- Name
0.07, !- Effective Leakage Ratio {dimensionless}
1.9, !- Maximum Flow Rate {m3/s}
15, !- Reference Pressure Difference {Pa}
0.65; !- Air Mass Flow Exponent {dimensionless}
The objects required for a complete set of inputs to simulate duct makeup air losses are listed below
Duct:Loss:Leakage
AirflowNetwork:Distribution:Linkage
AirflowNetwork:Distribution:Node
AirflowNetwork:Distribution:Component:LeakageRatio
Outputs
The simple duct model provides outputs described below.
HVAC,Average,Duct Loss Node Temperature [C]
HVAC,Average,Duct Loss Node Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,Duct Loss Sensible Loss Rate [W]
HVAC,Average,Duct Loss Latent Loss Rate [kgWater/s]
HVAC,Average,Zone Added Sensible Rate Due to Duct Loss [W]
HVAC,Average,Zone Added Latent Rate Due to Duct Loss [kgWater/s]
HVAC,Average,System Added Sensible Rate Due to Duct Loss [W]
HVAC,Average,System Added Latent Rate Due to Duct Loss [kgWater/s]
Duct Loss Node Temperature [C]
This is the simple duct model node temperature output in degrees C based on AirflowNetwork:Distribution:Node inputs.
Duct Loss Node Humidity Ratio [kgWater/kgDryAir]
This is the simple duct model node humidity ratio output in kgWater/kgDryAir based on AirflowNetwork:Distribution:Node inputs.
Duct Loss Sensible Loss Rate [W]
This is the duct loss sensible rate output in W for the simple duct model for each duct loss object.
Duct Loss Latent Loss Rate [kgWater/kgDryAir]
This is the duct loas latent rate output in kgWater/kgDryAir for the simple duct model for each duct loss object.
Zone Added Sensible Rate Due to Duct Losse [W]
This is a additional zone sensible load due to duct loss, summed by duct sensible loss from associated duct loss objects. The sensible load will be a part of zone energy balance.
Zone Added Latent Rate Due to Duct Loss [kgWater/kgDryAir]
This is a additional zone latent load due to duct loss, summed by duct latent loss from associated duct loss objects. The sensible load will be a part of zone moisture balance.
System Added Sensible Rate Due to Duct Loss [W]
This is a additional system sensible load due to duct loss, summed by duct sensible loss from associated duct loss objects. The sensible load will be a part of system energy load.
System Added Latent Rate Due to Duct Loss [kgWater/kgDryAir]
This is a additional system latent load due to duct loss, summed by duct latent loss from associated duct loss objects. The sensible load will be a part of system moisture load.